Supraharmonics within a Datacenter-Emission and Propagation
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.ORCID-id: 0000-0001-5558-7708
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.ORCID-id: 0000-0001-6074-8633
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.ORCID-id: 0000-0002-4004-0352
2022 (engelsk)Inngår i: 2022 20th International Conference on Harmonics & Quality of Power (ICHQP) Proceedings: “Power Quality in the Energy Transition”, IEEE, 2022Konferansepaper, Publicerat paper (Fagfellevurdert)
Abstract [en]

The reliability of the electrical and cooling systems is of utmost importance for the uninterrupted operation of the data center information technology (IT) load. The electrical distribution of the data center includes many subsystems starting with the utility and building transformers, uninterruptible power supply (UPS), power distribution units (PDUs), and power supplies ultimately powering the fans and the internal components of IT equipment. The various converters in data centers emit switching frequency residue due to PWM (pulse width modulation) techniques. The switching frequency range falls within the supraharmonic range, i.e., 2 to 150 kHz. This paper aims to show, with measurements, the different types of supraharmonic emissions measured in the data center, and the difference between their maximum and average magnitudes. The paper shows a method to identify the equipment emitting supraharmonic emission and possible disturbances caused by it. The paper traces the propagation of supraharmonic emission from the source through the transformer to the grid. Lastly, a comparison of measurements is made with the compatibility levels given by standard IEC 61000-2-2.

sted, utgiver, år, opplag, sider
IEEE, 2022.
Serie
International Conference on Harmonics and Quality of Power, ISSN 1540-6008, E-ISSN 2164-0610
Emneord [en]
Data center, Information technology, Power quality, Power supplies, Pulse Width Modulation, Supraharmonics
HSV kategori
Forskningsprogram
Elkraftteknik
Identifikatorer
URN: urn:nbn:se:ltu:diva-92095DOI: 10.1109/ICHQP53011.2022.9808561ISI: 000844604500029Scopus ID: 2-s2.0-85133789667OAI: oai:DiVA.org:ltu-92095DiVA, id: diva2:1681714
Konferanse
20th International Conference on Harmonics & Quality of Power (ICHQP 2022), Naples, Italy, May 29 - June 1, 2022
Forskningsfinansiär
Swedish Energy Agency, 43090-2
Merknad

ISBN för värdpublikation: 978-1-6654-1639-9

Tilgjengelig fra: 2022-07-07 Laget: 2022-07-07 Sist oppdatert: 2023-09-05bibliografisk kontrollert
Inngår i avhandling
1. On the supraharmonics in single-phase and three-phase installations
Åpne denne publikasjonen i ny fane eller vindu >>On the supraharmonics in single-phase and three-phase installations
2023 (engelsk)Doktoravhandling, med artikler (Annet vitenskapelig)
Abstract [en]

Society has increasingly started depending on the continuity of internet services, the interruption can be crucial for vital societal functions. It is therefore important to maintain continuous and reliable operations of e.g., installations housing sensitive IT (Information Technology) loads. The establishment of a data center attracts huge investments, thereby boosting the economy. The electrical load within the data center is more structured with a similar type of load, i.e., power supplies supplying the servers connected repetitively. They also use power-conditioning equipment such as an uninterruptible power supply (UPS), which ensures uninterrupted power to the servers. The power supplies use switching techniques to modulate and condition the power supplied to the IT load. The switching residues from the power supplies are often in the frequency range from 2 kHz to 150 kHz, known as supraharmonics. The switching frequency of power electronic converters and power line communication are identified as the main contributors to supraharmonics. The increase in the number of power electronic converters in the power system has sparked interest in supraharmonics. Limited standards are available on the magnitude of supraharmonics allowed in the system. For installations that house multiple power converters, prior knowledge about the propagation and consequences of the supraharmonics can be an advantage in increasing their reliability. This work is focused on supraharmonics within data centers, but the results of the study can be applied to other installations.

The data centers are usually three-phase installations where single-phase devices, i.e., servers are distributed over three phases. To understand the holistic view of the system, it is important to understand the spread of supraharmonics in phase, neutral, and protective earth conductors. A perspective on the behaviour of supraharmonics in three-phase installation is presented in this work. The focal point of the work is the summation of supraharmonics in the neutral conductor and conductor crosstalk. The behaviour of the device connected in single-phase installation and when the same devices are spread over three phases may differ depending on the design of the installation. Since the focus is on a greater number of devices, analysis for the change in the magnitude of supraharmonics in a neutral conductor with the change in the number of devices is also undertaken. The IT workload in a data center changes continuously, thus a constant unbalance in the electrical load between the three phases can exist. The thesis aims to understand the factors influencing the change in supraharmonic magnitude and propagation in phase and neutral conductors according to a balanced and unbalanced voltage supply and loading conditions. The presence of a supraharmonic emitting load in one phase can cause interference on the adjacent phase due to conductor crosstalk. Crosstalk leads to the propagation of supraharmonics between the phases. The work focuses on the parameters influencing the crosstalk phenomena for supraharmonics. Among the parameters studied, the type of cable used in an installation and the cable length is dominating. The measurement of supraharmonic emission from the device connected as single-phase and connected as three-phase would differ because of crosstalk.

A large number of servers in data centers connected close by may lead to an increased leakage current. The composite leakage current can comprise subharmonics, harmonics, and supraharmonics. This can cause unwanted tripping of the residual current device (RCD), which is installed for human protection. The work aims to understand the impact of the composite residual current on the operation of the residual current devices.

The main contributions of this work are summarized as:

• A sensitivity analysis is presented based on the parameters impacting the propagation of supraharmonics for different operating modes of a UPS.

• A characterization of supraharmonics emission from different devices according to their time and frequency varying behaviour.

• A mathematical model to predict the change in the supraharmonic emission in the neutral conductor.

• An increased understanding of the behaviour of supraharmonics for constant powerloads under voltage reduction conditions in three-phase installations.

• Introduction and definition of the terms induced primary emission and induced secondary emission to explain conductor crosstalk for supraharmonic emission.

• A mathematical model to show the factors influencing the magnitude of induced primary emission and induced secondary emission.

• The frequency response of RCDs of type AC, A, B, and F under residual currents comprising pure tones and composite currents is presented by measurements andmodeling.

sted, utgiver, år, opplag, sider
Luleå: Luleå University of Technology, 2023. s. 70
Serie
Doctoral thesis / Luleå University of Technology 1 jan 1997 → …, ISSN 1402-1544
HSV kategori
Forskningsprogram
Elkraftteknik
Identifikatorer
urn:nbn:se:ltu:diva-96668 (URN)978-91-8048-321-6 (ISBN)978-91-8048-322-3 (ISBN)
Disputas
2023-05-30, Hörsal A, Luleå tekniska universitet, Skellefteå, 09:00 (engelsk)
Opponent
Veileder
Tilgjengelig fra: 2023-04-20 Laget: 2023-04-19 Sist oppdatert: 2023-09-05bibliografisk kontrollert

Open Access i DiVA

Fulltekst mangler i DiVA

Andre lenker

Forlagets fulltekstScopus

Person

Sutaria, JilEspin Delgado, AngelaRönnberg, Sarah

Søk i DiVA

Av forfatter/redaktør
Sutaria, JilEspin Delgado, AngelaRönnberg, Sarah
Av organisasjonen

Søk utenfor DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetric

doi
urn-nbn
Totalt: 173 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf