CFD simulation and evaluation of different heating systems installed in low energy building located in sub-arctic climate
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.ORCID-id: 0000-0003-0225-711X
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.
Luleå tekniska universitet, Institutionen för teknikvetenskap och matematik, Energivetenskap.
2015 (Engelska)Ingår i: Building and Environment, ISSN 0360-1323, E-ISSN 1873-684X, Vol. 89, s. 160-169Artikel i tidskrift (Refereegranskat) Published
Abstract [en]

Computational Fluid Dynamics (CFD) simulations were used to study the indoor climate in a low energy building in northern Sweden. The building’s low heat requirement raise the prospect of using a relatively simple and inexpensive heating system to maintain an acceptable indoor environment, even in the face of extremely low outdoor temperature. To explore the viability of this approach, the indoor climate in the building was studied considering three different heating systems: a floor heating system, air heating through the ventilation system and an air heat pump installation with one fan coil unit. The floor heating system provided the most uniform operative temperature distribution and was the only heating system that fully satisfied the recommendations to achieve tolerable indoor climate set by the Swedish authorities. On the contrary, air heating and the air heat pump created a relatively uneven distribution of air velocities and temperatures, and none of them fulfills the specified recommendations. From the economic point of view, the air heat pump system was cheaper to be installed but produced a less pleasant indoor environment than the other investigated heating systems.

Ort, förlag, år, upplaga, sidor
2015. Vol. 89, s. 160-169
Nationell ämneskategori
Energiteknik
Forskningsämne
Energiteknik
Identifikatorer
URN: urn:nbn:se:ltu:diva-11144DOI: 10.1016/j.buildenv.2015.02.024ISI: 000364440600014Scopus ID: 2-s2.0-84924737867Lokalt ID: a0dde22a-a36f-4f00-a108-d848722aa479OAI: oai:DiVA.org:ltu-11144DiVA, id: diva2:984093
Anmärkning
Validerad; 2015; Nivå 2; 20150305 (andbra)Tillgänglig från: 2016-09-29 Skapad: 2016-09-29 Senast uppdaterad: 2018-07-10Bibliografiskt granskad
Ingår i avhandling
1. District heating system analysis and challenges within the urban transformation of Kiruna
Öppna denna publikation i ny flik eller fönster >>District heating system analysis and challenges within the urban transformation of Kiruna
2017 (Engelska)Doktorsavhandling, sammanläggning (Övrigt vetenskapligt)
Abstract [en]

There is currently an ongoing urban transformation in a small Swedish town named Kiruna, it is located in the very north of Sweden well above the Arctic Circle in a sub-arctic climate. Large part of the town will be relocated due to the ground deformation that is caused by the progressing iron ore mining activity and it is affecting all infrastructures of the town. This thesis aims to accomplish a holistic analysis on the district heating (DH) system for the town of Kiruna and its future challenges.

Energy companies with a DH system recognize the importance in having a good understanding about the network characteristics, for obtaining an efficient and stabile heat delivery to the end-users. In this thesis, a method for modeling and simulation of meshed DH networks is described, that makes it possible to study and analyze the flow pattern in order to locate non-obvious paths, bottlenecks and overloaded pipes.

For carrying out the DH simulations a fundamental input is to set the thermal losses for each pipe segment in the model, a fictitious series with all pipe diameters is created which corresponds to the annual losses in the real network. In comparison with the pipes series manufactured today the created one is best described by the series with least insulation and highest thermal losses. The studied network has its origin in the 60th and is the sum of the different piping technics that has been valid over time, this mixture is positioning the thermal performance as a close to a worst-case scenario.

To the meshed DH network a number of heat production sites are connected for delivering the thermal requested by the end-users, each site consisting of several boilers and using different resources. A hybrid evolutionary-Mixed Integer Linear Programing (MILP) optimization approach is developed and applied for finding the cost-optimal heat production for three scenarios in combination of two heating demand levels. It is stated that no matter the geographically location of the site the cheapest resource should always be favorable as fuel, in the case when the same resource is viable at different sites a differentiated heat production is obtained. The supply temperature from each site is found to be the one lowest possible in order to serve all site-concerned end-users with a temperature level high enough for hot water production. The findings recommend a network temperatures reduction with the consequence in higher cost related to pumping work, but is lower than the savings due to the reduction in thermal losses.

In order to provide the relocated part of the town with DH the hybrid evolutionary-MILP optimization routine is reshaped for finding different alternatives for network expansion layouts. The result is presented as a multi objective analysis between the operation cost and installation cost, showing the complete spectra of all optimal possible solutions and how the different cost correlate to each other. In this way, the outcome can be used for support in decision making, helping network owners is their planning and pipe sizing for new areas.

For constructing the buildings that will populate the new city-area the Swedish government has stated a number of recommendations for achieving livable thermal indoor climate. An investigation is carried out analyzing the impact from the usage of three different heating system; air/air heat pump, air heating and floor heating in a low energy family house, where the first two system are aimed to use heat from the DH network. The analysis show that only the floor heating system satisfies the recommendations stated, but with carefully planning an air heating system could also fulfill the recommendations. Further, a techno-economical evaluation declares that the cheapest heating cost over 30 years is by using an air/air heat pump. In order to make DH competitive as heating source the needed price reduction is found for the hydronic floor and air heating system.

Finally, three different building energy performance scenarios are studied in conjunction with the urban transformation in combination with the suggested energy measures from the Energy Performance certificates (EPC). In order to reach the national target entailing a reduction of 50% until 2050 all re-built buildings have to be built with passive standard and all advised measures in the EPC has to be carried out. Wort noticing is that the scenarios is analyzed as part of a 3-D City Model, which is found to be a worthwhile working tool for staff dealing with energy related issues.

Ort, förlag, år, upplaga, sidor
Luleå: Luleå University of Technology, 2017
Serie
Doctoral thesis / Luleå University of Technology 1 jan 1997 → …, ISSN 1402-1544
Nyckelord
District heating, analysis, optimization, design, heat production
Nationell ämneskategori
Energiteknik
Forskningsämne
Energiteknik
Identifikatorer
urn:nbn:se:ltu:diva-63091 (URN)978-91-7583-894-6 (ISBN)978-91-7583-895-3 (ISBN)
Disputation
2017-06-15, E632, Luleå, 09:00 (Engelska)
Opponent
Handledare
Tillgänglig från: 2017-04-24 Skapad: 2017-04-20 Senast uppdaterad: 2017-11-24Bibliografiskt granskad
2. Analysis of the Thermal Indoor Climate with Computational Fluid Dynamics for Buildings in Sub-arctic Regions
Öppna denna publikation i ny flik eller fönster >>Analysis of the Thermal Indoor Climate with Computational Fluid Dynamics for Buildings in Sub-arctic Regions
2018 (Engelska)Doktorsavhandling, sammanläggning (Övrigt vetenskapligt)
Alternativ titel[sv]
Analys av termiska inomhusklimatet med CFD för byggnader in subarktiskt klimat
Abstract [en]

This thesis aims to increase the knowledge of simulation of thermal indoor climate for nearly zero energy buildings in a sub-arctic climate. Air heating systems in cold climate generate temperature gradients, which negatively affects the thermal indoor climate. Stand-ard multi-zone modeling has problemswithpredicting these gradients.

In this work, Computerized Fluid Dynamics (CFD) simulations are used to model the tem-perature gradients. The consequences of reducing the cell sizes for the simulation volume are estimated and case studies of different building and heating systems are presented. The CFD method is validated for a traditional underfloor heating system and also for an air heating system.

Furthermore, the effects of snow on heat losses for common building foundations are in-vestigated, and snow is shown to be an important boundary for CFD simulations of a build-ing. The snow and ground freezing areshown to reduce the annual heat losses between 7-10%.

The CFD method is shown to be a suitable method for predicting thermal indoor climate. The method can determine the temperature variations inside a building, for different rooms, floors and heating systems. The CFD method is most appropriate for local distributed sys-tems. For traditional hydronic systems the method may be overambitious,since a good indoor climate is usually achieved anyway.

Heat transfer coefficients are inaccurate when calculated using standard wall functions used in many turbulence models (like the k-ε model) for surfaces with a high heat transfer rate and natural convection. Automatic wall functions have shown better accuracy for this type of problem, but they require more cells. In order to still use the k-εmodel, a user defined wall function is investigated. This method gave good results and a significant re-duction in the number of necessary cells in the simulation volume. The validation of the indoor climate shows that the wall boundary conditions are important for predicting the indoor temperaturevariations for steady state simulations.

New buildings have a higher thermal inertia, which affects the heat losses. It is important to include this effect in the boundary condition calculations for a CFD model.

The CFD simulations show that air heatingand local distributed heating systems have dif-ficulties infulfillinga good thermal comfort inside all rooms. This is especially true for rooms with exhaustair and closed doors and multi-storybuildings. Results from a CFD simulation can be used to improve the thermal comfort in these cases.

Ort, förlag, år, upplaga, sidor
Luleå: Luleå University of Technology, 2018
Serie
Doctoral thesis / Luleå University of Technology 1 jan 1997 → …, ISSN 1402-1544
Nationell ämneskategori
Energiteknik
Forskningsämne
Energiteknik
Identifikatorer
urn:nbn:se:ltu:diva-68067 (URN)978-91-7790-086-3 (ISBN)978-91-7790-087-0 (ISBN)
Disputation
2018-05-24, E632, 971 87, Luleå Tekniska Universitet, Luleå, 09:00 (Engelska)
Opponent
Handledare
Tillgänglig från: 2018-04-04 Skapad: 2018-03-27 Senast uppdaterad: 2018-05-17Bibliografiskt granskad

Open Access i DiVA

Fulltext saknas i DiVA

Övriga länkar

Förlagets fulltextScopus

Personposter BETA

Risberg, DanielVesterlund, MattiasWesterlund, LarsDahl, Jan

Sök vidare i DiVA

Av författaren/redaktören
Risberg, DanielVesterlund, MattiasWesterlund, LarsDahl, Jan
Av organisationen
Energivetenskap
I samma tidskrift
Building and Environment
Energiteknik

Sök vidare utanför DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetricpoäng

doi
urn-nbn
Totalt: 708 träffar
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • harvard1
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf