Fire Test of Profile Plank for Transformer Pit Fire Protection
SP Fire Research, SP Technical Research Institute of Sweden.
SP Fire Research, SP Technical Research Institute of Sweden.ORCID iD: 0000-0002-7140-4737
2016 (English)In: Fire technology, ISSN 0015-2684, E-ISSN 1572-8099, Vol. 52, no 2, 309-319 p.Article in journal (Refereed) Published
Abstract [en]

In general it is recommended to fill a transformer pit with rock ballast to extinguish the fire if there is a leakage of burning transformer oil. There is a lack of technology-neutral performance requirements for the design of solutions for fire extinguishment in transformer pit fires. This hampers the introduction of alternatives to the traditional method of filling the pit with rocks. Therefore we have conducted quantitative tests where temperatures and concentrations of CO, CO2, and O2 were measured at different position in a transformer pit subjected to burning oil simulating an accidental rupture and leakage. The tests were conducted to investigate the extinguishing capacity of one specific alternative solution, i.e. a profile plank layer over the pit. Three tests were performed with 90°C and 140°C pre-heated transformer oil. In the second test, a 19 cm water bed was used to examine the impact of rain water in the pit. The result showed that the profile plank extinguished the flames in a few seconds and that the water level did not have any significant effect on the result. The measurements showed that the temperatures peaked at 600–800°C 50 cm above the profile plank in all tests but dropped to under 100°C in 14–16 s. Furthermore the O2-concentration dropped to 3–5 vol% below the plank, which contributed to the rapid extinction of the burning oil.

Place, publisher, year, edition, pages
Springer, 2016. Vol. 52, no 2, 309-319 p.
National Category
Other Electrical Engineering, Electronic Engineering, Information Engineering Building Technologies
Research subject
Steel Structures
Identifiers
URN: urn:nbn:se:ltu:diva-64897DOI: 10.1007/s10694-014-0409-2ISI: 000371644500003Scopus ID: 2-s2.0-84959513395OAI: oai:DiVA.org:ltu-64897DiVA: diva2:1128144
Available from: 2017-07-21 Created: 2017-07-21 Last updated: 2017-08-16Bibliographically approved

Open Access in DiVA

No full text

Other links

Publisher's full textScopus

Search in DiVA

By author/editor
Försth, Michael
In the same journal
Fire technology
Other Electrical Engineering, Electronic Engineering, Information EngineeringBuilding Technologies

Search outside of DiVA

GoogleGoogle Scholar

Altmetric score

Total: 32 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard1
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf