66 tests of the influence of surface reinforcement on the tensile load capacity of cast-in fasteners have been carried through. In the tests threaded rods ∅30 mm with a ∅45 mm nut at the end were cast-in centrically in concrete slabs (1.2 m × 1.2 m × 0.3 m up to 2.2 m × 2.2 m × 0.6 m). The amount of surface reinforcement was varied from 0% up to about 1.2%. There is a considerable increase in the load capacity with surface reinforcement present. The increase depends on the geometry and the amount and placement of the reinforcement.